Cube Relay Repeat Cycle (Dual Adjustaable) OFF/ON Timers - TGKDDB Timers
Cube Relay Repeat Cycle (Dual Adjustable) OFF/ON Timers
|
|
 |
TGKDDB Timers
TGKDDB series Cube Relay Repeat-Cycle (Dual Adjustable) Off/On timers are a unique combination of solid-state timing circuitry with a relay output in a compact cube configuration. The time delay for both the “Off” cycle and the “On” cycle can be individually adjusted. These solid-state timers offer the many advantages of a relay output and provide the same functional performance as plug-in relay timers, but at a significant cost savings. |
Timing Mode
Application of power to the input voltage terminals starts the “Off” delay cycle, at the end of the “Off” cycle, load 1 is energized, this is the “On” cycle. At the end of the “On” cycle, load 1 de-energizes and another “Off” cycle starts. At the end of this “Off” cycle, load 2 is energized for an “On” cycle. This alternating output action continues until power is removed.
|
 |
|
FEATURES |
-
High current carrying capacity up to 10 amps
-
100% Load isolation
-
No leakage in N.O. position
-
No heat sinking required
-
Available in any time delay periods required
- Digital CMOS timing
|
-
Transient protected
-
No minimum load required
-
Totally encapsulated for protection from harsh environments
- 100% Operational testing before shipping

|
| BASIC WIRING AND DIMENSIONS |
 |
| SPECIFICATIONS |
|
Input Voltage:
- VDC: 12, 24
- VAC: 24, 48, 120, or 230, 50/60 Hz
Time Delay:
- Timing Mode: Repeat-Cycle Off/On Alternating
- Type: Digital CMOS
- Available Time Range: 0.2 seconds to 24 hours
- Time Adjustment:
- variable, with adjustments on timer
Repeatability: 0.5% Setting Accuracy:
- Fixed time period: 10% of nominal time,
- Variable time range:
- +15% -5% max. time, -10% min. time
Reset/Recycle Time: 100 milliseconds Initiate Time: 6 milliseconds or less Life Expectancy:
- Mechanical: 20 million operations
|
|
- Electrical: 100,000 operations at maximum load
- Contact Material: Silver nickel, gold plated, or silver cadmium oxide
Relay Output:
Rating:
- Standard – 6 amps (resistive)
- Optional – 10 amps (resistive)
Protection:
- Polarity Protection: All DC units have reverse polarity protection
- Transient Protection: 18 joules
- Dielectric Strength: 1800V RMS 60 Hz
Temperature Ranges:
- Storage: -40° C to +85° C
- Operating: -40° C to +85° C
Physical Data:
- Mounting: Surface with one #8 screw
- Connection & Termination: 0.25" quick connects
|
| SELECTION PROCEDURE |
| Mode of Operation |
Series |
Input Voltage |
Time Ranges |
Time Adjustment Method |
Relay Output Form |
Options |
Repeat-Cycle Off/On (Dual Adjustable) |
TGKDDB |
- 120 VAC
- 230 VAC
- 24 VAC
- 24-28 VDC
- -
- -
- 12 VDC
- Any in between AC voltage (specify)
- Any in between DC voltage (specify)
|
|
VARIABLE TIME PERIODS
|
0001 .05 to 1 sec. 0010 .1 to 10 sec. 0100 1 to 100 sec. 1000 10 to 1000 sec.
Any range up to 24 hours available on special order.
|
|
FIXED TIME PERIODS
|
Specify time in full seconds or hours followed by the letter “S” or “H” and the decimal amount of the main time unit.
Examples:
- 5S5 is 5.5 seconds
- 5H5 is 5.5 hours
|
|
- Variable, integral, knob on timer.
- -
- Fixed, internal, factory set.
|
- SPST
|
- Heavy Duty,10 amps (6 amps relay standard)
|
|
|