| CW-6161 Magnetic Control Relay |

Download technical data |
| Electrical Inputs (Low Voltage)
|
± 24 VDC, rectified half-waves, reverse polarity. Class II, 350 mA current |
| Electrical Outputs (Line Voltage)
|
- Resistive load: 20 A, 347 Vac
- Inductive load: 20 A, 347 Vac
- Incandescent lamp: 20 A, 120 Vac
- Fluorescent lamp: 20 A, 347 Vac
- H.I.D Lamp: 20 A, 347 Vac
- Motor: 1-1/2 HP at 220-277 Vac (general use).
- Motor: 1/2 HP at 120 Vac (tungsten) |
| Operation
|
- A positive pulse of -18 to -30 Vdc opens the relay and disables the load (Off action)
- A negative pulse of -18 to 30 Vdc closes the relay and enables the load (On action)
|
| Test condition
|
- Reliable contact opening mechanism for 30,000+ On/Off cycles on a full 20 A HID charge at 347 Vac (20 times/minute switching cycle)
- High in-rush duty (HID) : Flawless operation up to 1,500 A for 20 milliseconds
- Ambient temperature: -30° C to 50° C |
| Override switch
|
Manual On/Off operation lever (integral to the relay) |
| Status indicator
|
Visual mechanical indicator of status (On or Off) |
| Wiring
|
Two-wire for both pulse activation and state return command for automatic monitoring through a control panel indicator lamp or a host PC |
| Mounting
|
Adapter mounted for easy removal. Mounts on WR-9910 Mounting Strap. Requires one space |
| Auxiliary contact (optional)
|
0.5 A, 125 Vac
|
| Weight in lb (kg)
|
0.437 (0.198) |
| Certification
|
Underwriters Laboratories (UL) listed |